Specialists for Commercial, Industrial & Residential Projects

A Simple Guide to LED Emergency Signs and Lights

Emergency lighting is designed for the moment when normal lighting fails, whether through a power cut, an electrical fault or a fire. It must switch on automatically and provide enough light for everyone to leave the building safely, or to shut down a dangerous process before they go. LED technology has made emergency lighting more efficient, compact and reliable. This guide explains the basics.

Types of emergency lighting

Emergency lighting is generally divided into two categories.

Emergency escape lighting

This is the part of the system that keeps people safe. It includes:

  • Escape route lighting: lights corridors, stairs and exits so people can find their way out and use the route safely.
  • Open area (anti-panic) lighting: provides enough light in larger rooms and halls for people to reach an escape route without panic.
  • High-risk task area lighting: allows people working with dangerous machinery or processes to make them safe before leaving.
  • Exit signs: illuminated signs, using the familiar green “running man” pictogram, that show the direction to the nearest exit.

Standby lighting

Standby lighting allows normal activities to continue, more or less unchanged, during a power failure. Hospitals, data centres and some industrial processes use it. Standby lighting is not a substitute for escape lighting, and it usually relies on generators or large battery systems.

Maintained and non-maintained fittings

  • Maintained fittings are on all the time and stay on when the mains fails. They are common in places of public assembly such as cinemas, theatres, restaurants and hotels, and for exit signs that must always be visible.
  • Non-maintained fittings stay off during normal operation and only light up when the power fails. They are typical in offices, factories and apartment block common areas.

Many standard LED luminaires, such as panels, downlights and battens, can also be supplied with an emergency conversion kit so that the same fitting works as both normal and emergency lighting.

Self-contained or central battery?

There are two main ways to power emergency lighting:

  • Self-contained systems: each fitting has its own battery and charger. They are quick to install, use standard wiring and need no special sub-circuit, and a fault affects only one fitting. This makes them the most popular choice for small and medium buildings. The trade-off is that batteries are spread throughout the building, need periodic replacement and can be affected by very high or low ambient temperatures.
  • Central battery systems: a single battery bank powers all emergency fittings through dedicated fire-resistant wiring. They cost more to install but centralise maintenance and testing, which can make sense for large or complex buildings.

The right choice depends on the building’s size, layout and how it will be maintained.

Why LED is the right technology

  • LEDs draw little power, so batteries can be smaller or last longer.
  • They reach full brightness instantly, which is essential in an emergency.
  • Long LED life means less maintenance of the light source itself.
  • Compact LED fittings and signs are discreet and easy to integrate into modern interiors.

Quality matters. Choose fittings from reputable manufacturers that have been tested to the relevant European standards, with batteries and drivers designed to cope with heat. In Malta’s summer, ceiling voids and corridors can get very warm, and high temperatures shorten battery life.

Standards and requirements

In Europe, emergency lighting design is guided mainly by EN 1838 (which sets out light levels and how they are applied) and EN 50172 (which covers the system, including installation and testing). Some widely used benchmarks include:

  • A minimum of 1 lux along the centre line of escape routes.
  • A minimum of 0.5 lux across open areas.
  • A minimum duration of at least one hour, with three hours often required, for example in premises with sleeping accommodation or where people may re-occupy the building after an incident.
  • Emergency lights at key points: every exit door, each change of direction, stairs, changes of floor level, near fire-fighting equipment and first aid points.

Exact requirements depend on the type of building and its use, and on local fire-safety regulations and the fire risk assessment. Always follow the advice of your architect, fire-safety consultant and the relevant authorities.

Consultation and design

The first step in any emergency lighting project is consultation and design. The fire risk assessor and the lighting designer should agree where emergency lighting is required and produce a plan showing the power supply type, the areas covered, the duration and the mode of operation. A lighting calculation can confirm that light levels along escape routes and in open areas meet the standard. Ideally, emergency lighting is designed together with the general lighting scheme, as we describe in our simple guide to office lighting design.

Emergency lighting is a priority for anyone building or renovating apartment blocks, offices, shops or industrial premises. It is far easier and cheaper to plan it properly from the start than to add it later.

Testing and maintenance

Emergency lighting only protects people if it works when needed. Typical practice includes:

  • A brief monthly function test to check that each fitting switches to battery.
  • An annual full-duration test to confirm batteries last for the rated time.
  • A logbook recording tests, faults and repairs.

Self-test fittings can carry out these tests automatically and indicate faults, which saves time in larger buildings. Testing does require care, as fittings need time to recharge afterwards, so full-duration tests are best scheduled when the building is lightly occupied.

RG Alternatives supplies LED emergency lights, exit signs and emergency conversion options, and can advise on the right solution for your building as part of a wider lighting project. Book a consultation or call us on +356 2141 4137.

About Us

RG Alternatives has supplied, designed and installed LED lighting across Malta since 2011 — from factories, hangars and airports to showrooms, shops and homes. Visit our showroom, LTC LED Lighting, in Naxxar.